SF6 Micro Water Density Online Monitoring System ACDC-JC-G301 | |
Measurement Range | 0.01-1.00 MPa |
Measurement Accuracy | ±0.5% F.S. |
Alarm Threshold | 0.45 MPa (Adjustable) |
Lockout Threshold | 0.40 MPa (Adjustable) |
Temperature Specifications | Temperature Measurement Range: -50ºC to +99ºC |
Temperature Measurement Accuracy: ±1ºC | |
Other Specifications: | |
Alarm Contact Capacity | AC220V/7A, Normally Open (NO) / Normally Closed (NC) |
Communication Interface | Isolated RS-485 |
Power Supply Voltage | 24VDC or 85V-265VAC |
Operating Environment | Temperature: -30ºC to +65ºC |
Humidity: ≤95% RH | |
Insulation Performance | |
Between Enclosure and Power Supply | 10MΩ |
Dielectric Strength | |
Between Enclosure and Power Supply | 2000V |
Electromagnetic Compatibility (EMC) Characteristics | |
Electrical Fast Transient/Burst Immunity | GB/T 17626.4-1999 Level 3 |
Surge (Lightning) Immunity | GB/T 17626.5-1999 Level 3 |